In-building Emergency Responder Communications Enhancement Systems
Supports All Frequency Bands
The M5 can support any public safety Land Mobile Radio (LMR) frequency band within the same product platform. The standard DSP channelized models can be programmed for up to 32 Channels and can be configured with up to 64 channels if needed. The Dual band DSP versions come with 64 Channel capacity as standard. Class B-ANA models are band selective and can be factory tuned for a specific frequency band. Frequency bands can easily be changed on all models with a simple panel swap. Duplexers are built-in on the BDA panel and no external filters are required for standard operation.
| Band | Uplink | Downlink |
| VHF | 150MHz – 170MHz | 150MHz – 170MHz |
| UHF | 406.2MHz-512MHz | 406.2MHz – 512MHz |
| 700MHZ | 799MHz – 805MHz | 769MHz – 775MHz |
| 800MHz | 806MHz – 824MHz | 851MHz – 869MHz |
700/800MHz Dual Band | 799MHz – 805MHz 806MHz – 824MHz | 769MHz – 775MHz 851MHz – 869MHz |
Supervision and Monitoring
The M5 includes supervision and monitoring compliant with the requirements of NFPA1225, 1221, 72, IFC, and UL2524. Fire Alarm Monitoring Modules connect directly to the provided normally open relay output “dry contacts” with built-in EOL resistors: AC Power, BDA Trouble, Charger Trouble, Battery Low, Antenna Trouble, System Component Trouble, Oscillation Detected, and a programmable Auxiliary port that can be programmed for different functions, including the enclosure door / tamper alarm. The Standby switch terminal is available in case the AHJ requires BDAs to remain in standby mode and to be activated only when needed. When in STBY mode, the BDA is still fully supervised and batteries are still being charged. Also, important to mention is that In addition to supervising the Donor Antenna, M5 can supervise the DAS Riser.

Dedicated Annunciator Panel
The M5 series offers two Dedicated Annunciator Panel options: the Standard Version and the Enhanced Version. Both versions are code-compliant and fully supervised. They are very simple to install on a standard two-gang / four-gang electrical box and connect to the BDA with a standard four-wire twisted pair fire alarm cable. No external power supply, no configuration, or programming is required – just connect the four wires. The Enhanced Version adds an audible alert and a “lamp test” function which is required in some jurisdictions.





The new standard in life safety systems. The Siemens FireFinder XLS is the most responsive intelligent fire detection system, with unrivaled speed, detecting fire and notifying occupants in under 3 seconds and it’s the simplest intelligent system to install and maintain.
Cerberus PRO is the ideal solution for each application. From a simple building to widely distributed or complex buildings. From clean environments to harsh environments. Cerberus PRO is an intelligent fire protection system for fast, reliable fire detection, alarm signaling, and control for your customers. Its wide portfolio comprises innovative products with intelligent technology. Multi-criteria detectors with our unique ASAtechnology offer advanced signal processing, selectable detection profiles, and carbon monoxide life safety detection. This provides maximum safety and enhanced protection of people and assets, without the threat of false alarms.
Cerberus PRO is an intelligent fire protection system for fast, reliable fire detection, alarm signaling, and control for your customers. Its wide portfolio comprises innovative products with intelligent technology. Multi-criteria detectors with our unique ASAtechnology offer advanced signal processing, selectable detection profiles, and carbon monoxide life safety detection. This provides maximum safety and enhanced protection of people and assets, without the threat of false alarms.The Cerberus PRO FC901 offers a cost effective, stand-alone fire control panel that can connect up to 50 detectors and peripheral devices.